Allen Bradley PLC File Data Address

Help Contents

Introduction

The Allen Bradley PLC File Data Address defines the location of data in an Allen Bradley file based PLC.

Allen Bradley file based PLC models include:

These types of PLC are configured using ladder logic and store data in files.

To access data in a file based PLC, Fernhill SCADA uses this format of data address:

Xf:e.w/b

Where:

File Type

Data in Allen Bradley PLC Devices is stored in files. For example, there are separate files for Inputs, Outputs, Status Bits, Timers, Counter, Integers and so on. Some file types are fixed, for example there can only be one file each for Inputs, Outputs and Status Bits. Other files are more flexible, for example there can be multiple Integer files.

File TypeNotes
O Outputs If used, the File Number must be 0.
The Element Number sets the I/O slot.
The Word Offset sets the word offset within the I/O slot.
The Bit Offset sets the bit number (0-15).
I Inputs If used, the File Number must be 1.
The Element Number sets the I/O slot.
The Word Offset sets the word offset within the I/O slot.
The Bit Offset sets the bit number (0-15).
S Status If used, the File Number must be 2.
The Element Number sets the status word.
The Bit Offset sets the bit number (0-15).
B Bit The File Number sets which bit file to use (3, 9-255). If not used, the File Number is 3.
For bit addresses, the Element Number is optional:
  • When an Element Number is used: The Element Number sets the word and the Bit Offset sets the bit number (0-15).
  • If the Element Number is not used: The Bit Offset sets the bit number (0-65535).
For example: B/81 is logically equivalent to B:5/1.
T Timer The File Number sets which timer file to use (4, 9-255).
If not used, the File Number is 4.
The Element Number sets the timer index.
The Word Offset sets the word offset within the timer (0-2).
The Bit Offset sets the bit number (0-15).
C Counter The File Number sets which counter file to use (5, 9-255).
If not used, the File Number is 5.
The Element Number sets the counter index.
The Word Offset sets the word offset within the counter (0-2).
The Bit Offset sets the bit number (0-15).
R Control The File Number sets which control file to use (6, 9-255).
If not used, the File Number is 6.
The Element Number sets the control index.
The Word Offset sets the word offset within the control (0-2).
The Bit Offset sets the bit number (0-15).
I Integer The File Number sets which integer file to use (7, 9-255).
If not used, the File Number is 7.
The Element Number sets the word.
The Bit Offset sets the bit number (0-15).
F Float The File Number sets which float file to use (8-255).
If not used, the File Number is 8.
The Element Number sets the float index.
ST String The File Number sets the which string file to use (9-255).
The Element Number sets the string index.
The Word Offset sets the word offset within the string (0-41).

File Number

In an Allen Bradley PLC, data is organized as files. The File Number is optional and, if included, sets which file to access. If the File Number is not included the file number is implied by the File Type. All PLC Devices have a predefined set of files as follows:

FileType
0Outputs
1Inputs
2Status
3Bit
4Timer
5Counter
6Control
7Integer

Notes:

  1. On a MicroLogix 1000 PLC no additional files can be defined.
  2. On a MicroLogix 1200 PLC, SLC 5/01 CPU, or SLC 5/02 CPU file 8 is reserved. Additional file numbers 9 to 255 are user defined.
  3. On a other PLC types file 8 is a Float file. Additional file numbers 9 to 255 are user defined.

Element Number

The Element Number sets which element of the file to access.

For Input and Output files, the Element Number indicates which I/O slot to access. An I/O slot may consist of 1 word, or multiple words depending on the type of I/O configured.

For other file types, the Element Number sets which element to access.

Word Offset

The Word Offset field is optional, and if used, defines which word of a multi-word element to access.

Bit Offset

The Bit Offset field is optional, and if used, defines which bit of the word to access.

Data Address Editor

The Data Address Editor provides a convenient tool to build Allen Bradley File Data Address strings.

To open the File Data Address Editor, click the Browse button Browse button of the DataAddress property:

Allen Bradley Data Address Editor

File Data Address Examples

Some examples of Allen Bradley File Data Addresses:

AddressDescription
O:1, O0:1, O:1.0The first word of output slot 1.
O:1/0, O0:1/0, O:1.0/0The first bit of the first word of output slot 1.
I:5.1, I1:5.1The second word of input slot 5.
B:5/1, B3:5/1Bit 1 of word 5 of the default binary file.
B/81, B3/81Bit 1 of word 5 of the default binary file.
N:20, N7:20Word 20 of the default integer file.
N:20/15, N7:20/15Bit 15 of word 20 of the default integer file.
N10:15Word 15 of user defined integer file 10.

Where Used

The Allen Bradley PLC File Data Address is used in these contexts:

Further Information

Allen Bradley Logix Data Address

To learn about accessing data in Allen Bradley Logix PLC

Allen Bradley Register Block Tag

To learn about Allen Bradley Register Block Tags.

Allen Bradley Driver

For an overview of the Allen Bradley Driver.